Cooling towers run hard in Dubai for most of the year, and warm, recirculating water full of airborne dust is where Legionella grows. Dubai Municipality sets out what building owners must do about it in one document: the Technical Guidelines for Legionella Control in Water System. This guide turns the cooling tower parts of that document into a schedule, a set of action levels and a record list an FM team can run, with a worked example of what to do when a result comes back high.
Key takeaways
- Clean and disinfect every six months at least, and before restarting any tower that has been off for more than four days.
- Test monthly and quarterly: total bacteria count every month, Legionella every quarter, by an EIAC-accredited laboratory.
- 1,000 cfu/l is the reporting line. A Legionella result at or above it goes to Dubai Municipality within 24 hours, and the tower needs emergency decontamination.
- Records are part of compliance. Daily disinfectant and ORP readings, risk assessment, cleaning and test records, submitted every two weeks.
The Rule Book and Who It Applies To
Everything in this guide comes from Dubai Municipality's Technical Guidelines for Legionella Control in Water System (document DM-HSD-GU44-LCWS2, version 6, issued 19 August 2025 by the Health and Safety Department). It covers cooling towers and evaporative condensers, hot and cold water systems, fountains, spas and evaporative coolers. This article deals with cooling towers and evaporative condensers only. If your building is in another emirate, check the local authority's own requirements; we have not covered them here.
The duty sits with the owner, principal manager or person in charge of the premises. The guideline asks them to name a person responsible for Legionella control, trained in it, and to carry out a written risk assessment of every water system at least once a year, or sooner when the system changes. In practice an FM contractor or a water treatment specialist does most of the work, which is why the contract has to say who does each task and who keeps each record.
The Cooling Tower Maintenance Schedule
The guideline does not publish a single schedule table, so we have pulled the cooling tower duties from its sections 11, 12, 13 and 15 into one. Each line is a task you can load as a planned preventive maintenance job.
| Frequency | Task | Section |
|---|---|---|
| Daily | Read and log disinfectant level (ppm) and ORP for each tower and the make-up water tank, on the guideline's Schedule 2 sheet | 22 |
| Weekly | Visual inspection to stop dirt, organic matter and debris building up | 12-1 |
| Monthly | Competent person inspects the automatic water treatment system | 15 |
| Monthly | Sample and test the total (aerobic) bacteria count | 13-2, 15 |
| Quarterly | Sample and test for Legionella: one sample from each collection basin and each make-up water tank | 13-1, 13-2 |
| Every 6 months | Empty, clean and disinfect the whole cooling water system: tanks, pumps, pipes, filters, fittings | 12-1, 15 |
| Yearly | Review the written risk assessment, schematic and sampling point layout | 11 |
| On event | Clean before restart after a shutdown of more than four days; clean and disinfect whenever Legionella is detected | 12-1, 15 |
Two design requirements sit alongside the schedule. Every cooling water system, including its make-up tanks, must have an automatic biocide dosing device that works all year, and every tower must have drift eliminators and be placed so the drift blows away from air intakes, opening windows and building entrances. If a tower fails either, that is a capital item, not a PPM task, and it belongs on the risk assessment until it is fixed.
Sampling and Testing
The guideline is specific about how testing is done, and an auditor will check the lab report against it:
- Method. Legionella is counted by culture of viable organisms to ISO 11731. Sampling should follow BS 7592.
- Laboratory. Analysis must be done by a lab accredited by the Emirates International Accreditation Centre (EIAC) for that test.
- Sampling points. At least one sample from each tower collection basin and one from each make-up water tank, at points set out in the risk assessment.
- Limits. For cooling water, Legionella should not exceed 1,000 cfu per litre and the aerobic count should stay below 10,000 cfu per ml.
Note the units: Legionella is reported per litre, the aerobic count per millilitre. A lab report that mixes them, or a CAFM reading field without a unit, is a common source of wrong decisions.
Action Levels After a Test
Table 4 of the guideline sets out what to do for each band of results. We have kept its wording close to the original.
| Aerobic count (cfu/ml) | Legionella (cfu/l) | Action |
|---|---|---|
| Below 5,000 | Not detected | Acceptable. |
| 5,000 to 10,000 | 100 or less | Continue routine maintenance and inspection. |
| 10,000 to 100,000 | 100 to 1,000 | Review dosing, biocide level and pH, and the risk assessment. Resample. If a similar count comes back, clean and disinfect the tower and resample. Keep remedial action going until Legionella is below 100 cfu/l and the aerobic count below 10,000 cfu/ml. |
| Above 100,000 | Above 1,000 | Turn the tower off. Clean and disinfect immediately and resample. Review the risk assessment, dosing and pH, and add an alternative biocide. Restart only when Legionella is below 100 cfu/l and the aerobic count below 10,000 cfu/ml. |
The 24-hour rules
The emergency disinfection in section 18-1 is also prescriptive: shut the system off and isolate the fans, circulate a dispersant, dose sodium hypochlorite to hold 5 to 10 mg/l free chlorine at pH 7.0 to 7.6 for at least 60 minutes (checked every 15 minutes), drain, clean all wet surfaces, refill and hold 1 to 5 mg/l for at least 30 minutes, then drain, refill and recommission with the water treatment programme restarted. When results fall in different rows of the table, our advice is to act on the more serious row.
Worked Example: A High Result at a Hotel
A hotel runs two cooling towers. The quarterly lab report for Tower 2 shows an aerobic count of 32,000 cfu/ml and Legionella at 400 cfu/l. Tower 1 is within limits. Here is how the guideline plays out, step by step:
- Band. Both readings fall in the third row: review and resample. Legionella is below 1,000 cfu/l, so there is no 24-hour report and no forced shutdown yet.
- Review. The water treatment contractor checks the daily log. ORP on Tower 2 has drifted low for ten days and the dosing pump has an open fault. The pump is repaired and dosing brought back into range.
- Resample. A resample is taken from the Tower 2 basin and sent to the EIAC-accredited lab.
- Second result. It comes back at 28,000 cfu/ml and 300 cfu/l, a similar count. The guideline now requires cleaning and disinfection of the tower, followed by another resample.
- Close-out. Tower 2 is cleaned and disinfected, the next result shows Legionella not detected and an aerobic count of 3,000 cfu/ml, and the risk assessment is updated to note the dosing pump failure and a new weekly check on it.
If the first result had shown 1,500 cfu/l, the hotel would have turned Tower 2 off, started emergency decontamination, and sent the lab report to Dubai Municipality within 24 hours. For a hotel or hospital, that is also the point to involve the infection control or guest safety lead.
Records Dubai Municipality Expects
Section 12-3 lists the records the premises must hold. Use it as an audit checklist:
- A formal risk assessment and scheme of control for operation, maintenance and monitoring.
- A layout of sampling points based on the risk assessment survey.
- System schematics and operation and maintenance manuals.
- The system water volume, with the date and method used to work it out.
- Dates and results of every inspection, maintenance task and disinfection.
- Treatment procedures, the biocide in use and its safety data sheets.
- Names of the people responsible for running and shutting down the system.
- All test results, including microbiological reports.
The guideline asks for these records to be available for inspection and submitted every two weeks to ehcinspection@dm.gov.ae. The daily disinfectant and ORP sheet (Schedule 2 in section 22) is the record most often missing or filled in after the fact, so treat it as a daily task with a named person, not a form in the plant room.
Running It as PPM in a CAFM
Paper logs and a spreadsheet of lab results can meet the rule, but they make it hard to prove. A CAFM gives each tower an asset record and turns the schedule above into jobs that cannot be quietly skipped:
- One asset per tower and make-up tank, each with its PPM tasks at the frequencies above.
- Readings on the job. The daily ppm and ORP, and each lab result with its unit, entered against the asset so trends show before a test fails.
- Event jobs. A result in the third or fourth band opens a corrective job for resampling or decontamination, with its own deadline.
- Evidence. Photos before and after cleaning, the technician's sign-off and the lab report attached to the job, as set out in our guide to technician proof of work.
How Reflexion handles statutory PPM
Want your cooling tower PPM audit-ready?
Bring your current schedule and a recent lab report. We will show how the tasks, readings and records sit in Reflexion.
Frequently Asked Questions
How often must a cooling tower be cleaned in Dubai?
Dubai Municipality's Technical Guidelines for Legionella Control in Water System (DM-HSD-GU44-LCWS2, version 6, August 2025) require every cooling water system, including its tanks, pumps, pipes, filters and fittings, to be emptied, cleaned and disinfected at least once every six months, and whenever Legionella is detected. A system shut down for more than four days must be cleaned before it is restarted.
How often should cooling tower water be tested for Legionella in Dubai?
The guideline sets Legionella testing quarterly and the aerobic (total) bacteria count monthly for cooling water. Testing must follow ISO 11731 by culture, sampling should follow BS 7592, and the laboratory must be accredited by the Emirates International Accreditation Centre (EIAC).
What Legionella level must be reported to Dubai Municipality?
If a test report shows 1,000 or more colony forming units of Legionella per litre in a cooling water system, the owner must submit the report to Dubai Municipality's Health and Safety Department within 24 hours of receiving it. Any confirmed case of Legionnaires' disease on the premises must also be reported within 24 hours.
What records does Dubai Municipality expect for cooling towers?
A current risk assessment and scheme of control, a system schematic with sampling points, operation and maintenance manuals, the system water volume, inspection and cleaning records, biocide details with safety data sheets, the names of responsible staff and all test results. The guideline asks for these to be available for inspection and submitted every two weeks to ehcinspection@dm.gov.ae, and it includes a daily log template for disinfectant level and ORP per tower.
Who is responsible for Legionella control in a building?
The guideline places the duty on the owner, principal manager or person in charge of the premises. They must name a person responsible for Legionella control who is trained in it. Where an FM contractor runs the plant, the contract should say who holds each task, test and record, but the duty to comply stays with the premises.
Source
Dubai Municipality, Health and Safety Department. Technical Guidelines for Legionella Control in Water System, DM-HSD-GU44-LCWS2, version 6, 19 August 2025. Check Dubai Municipality's site for later versions before relying on a specific figure.